METRALINE ZCHECK Loop Resistance Measuring Instrument
METRALINE ZCHECK Loop Resistance Measuring Instrument
The following measurements can be performed with the METRALINE ZCHECk:
• Fault loop impedance with short-circuit current• Fault loop impedance with short-circuit current without tripping the RCCB
• Line impedance with short-circuit current
• Line voltage
• Phase detection
Features of METRALINE ZCHECK
• Table of common protective devices can be displayed• Digital display, backlit color OLED display, switching between brief and detailed representation
• LED for measurement point illumination
• Patented means of securing test probes
• Compact and rugged – for service calls and laboratory use
Applications of METRALINE ZCHECK
The METRALINE ZCHECk allows for the evaluation of measured imped- ance in consideration of type, nominal current and disconnection time. A table with the parameters of various protective devices is included in device memory.Applicable Regulations and Standards of METRALINE ZCHECK
IEC 61010-1/-031 DIN EN 61010-1/-031 VDE 0411-1/-031 |
Safety requirements for electrical equipment for mea- surement, control and laboratory use Part 1: General requirements Part 31: Safety requirements for hand-held probe as- semblies for electrical measurement and test |
IEC 61557-1/-3 DIN EN 61557-1/-3 VDE 0413-1/-3 |
Electrical safety in low voltage distribution systems up to 1000 V AC and 1500 V DC – Equipment for testing, measuring or monitoring of protective measures Part 1: General requirements Part 3: Loop resistance |
IEC 61326-1 DIN EN 61326-1 |
Electrical equipment for measurement, control and labo- ratory use – EMC requirements Part 1: General requirements |
DIN EN 60529 VDE 0470-1 |
Degrees of protection provided by enclosures (IP code) |
Characteristic Values
Fault Loop Impedance / Line ImpedanceNominal Range per EN 61557-3: 0.27 W to 200 W
Range (W) | Resolution (W) | Intrinsic Uncertainty | Measuring Uncertainty |
0.00 to 4.99 | 0.01 | ±(3% rdg. + 5 d) | ±(4 % rdg. + 7 d) |
5.0 to 49.9 | 0.1 | ±(3% rdg. + 3 d) | ±(4 % rdg. + 4 d) |
50 to 200 | 1 | ±3% rdg. | ± 4 % rdg. |
Voltage range: 190 to 260 V / 48 to 52 Hz
Load resistance: 50 W (variable number of pulses at 10 ms)
Fault Loop Impedance Without Tripping the RCCB
for measurements of RCCBs with a nominal current of 100 mA or 300 mA
Nominal Range per EN 61557-3: 0.8 W to 200 W
Range (W) | Resolution | Intrinsic Uncertainty | Measuring Uncertainty |
0.0 to 4.9 | 0.1 W | ±(5% rdg. + 2 d) | ±(6% rdg. + 2 d) |
50 to 200 | 1 W | ± 7% rdg. | ± 8% rdg. |
Voltage range: 190 to 260 V / 48 to 52 Hz
Load resistance: 50 W (variable number of pulses and pulse width)
Short-Circuit Current
Range | Resolution | Intrinsic Uncertainty | Measuring Uncertainty |
0 to 999 A | 1 A |
Depending on measuring error for loop impedance ±1 d |
Depending on measuring error for loop impedance ±1 d |
1.0 to 9.9 kA | 0.1 kA | ||
10 to 23 kA | 1 kA |
Range | Resolution | Intrinsic Uncertainty | Measuring Uncertainty |
24 to 260 V |
1 V 0.1 V |
±(2 % rdg. + 2 d) | ±(3% rdg. + 3 d) |
Frequency range: 48 to 52 Hz
1 Display for brief representation
2 Display for detailed representation
Key:
a) The measuring uncertainties specified here for fault loop impedance, line imped- ance and short-circuit current are only valid if line voltage is stable during measure- ment and if no other electrical circuits parallel to the measured circuit are in use.
c) rdg. means reading, i.e. measured value, d = digits (i.e. number of the decimal place with the least significance)
Reference Conditions
Temperature 23 ±2 °C Relative humidity 40 to 60%Line voltage 230 V ±2% / 50 Hz ±1%
Device position any
Ambient Conditions
Operating Conditions
Operating
temperature 0 to 40 °C
Relative humidity max. 85%, no condensation allowed Line voltage 190 to 260 V / 48 to 52 Hz
Device position any
Storage Conditions
Temperature –10 to +70 °C
Relative Humidity max. 90% at –10 to +40 °C
max. 80% at +40 to +70 °C
Device position any
Power Supply
Batteries 4 ea. AAA (LR03), 1.5 V alkaline or 1.2 V NIMH (with at least 750 mAh)Number of measurements with batteries at 800 mAh:approx. 3,000 measurements
Electrical Safety
Measuring category with safety cap applied to test probe:CAT III 300 V
without safety cap applied to test probe: CAT II 300 V
Pollution degree 2
Protection class II
Fuse SIBA ceramic fuse
6.3 mmx32 mm, F1 A/600 V switching capacity 50 kA at 600 V
Electromagnetic Compatibility (EMC)
Interference emission EN 61326-1:2006 class B Interference immunity EN 61326-1:2006Mechanical Design
Display OLED, multicolored, graphicProtection Housing: IP 43
per DIN VDE 0470 part 1/EN 60529
Dimensions approx. 260x70x40mm
Weight approx. 0.36 kg with batteries
Scope of delivery
1 Test instrument with mobile test probe4 Batteries (AAA)
1 Pouch
1 Condensed operating instructions
1 CD ROM with operating instructions in available languages
1 Factory calibration certificate
Order Information
Description | Type | Article number |
Loop Resistance Measuring Instrument | METRALINE ZCHECK | M507A |
Broad-range charger for charging option- ally available batteries, e.g. Z507B, in- serted in the METRALINE ISO-RCD-Z CHECK Input*: 100 to 240 V AC ±10%; Output: 9 V DC, 180 mA |
Charger METRALINE CHECK Series | Z507A |
4 rechargeable batteries (AAA) for METRALINE ISO-RCD-Z/CHECK |
Akku-Set METRALINE CHECK Series |
Z507B |
For more information, please click GMCI